Skip to content
09 / Commercial · Diagnostic & repairs

Commercial Fault Finding & Repairs.

SQUARE.01
FIELD.APV ARRAY

Faults on commercial sites are usually trading-hour disruptions, not life-safety emergencies — but the fix needs to be permanent, documented, and not in the way of the next trading day. We diagnose and repair commercial electrical faults with thermal imaging, three-phase analysis, and written incident records.

02How the job runs

From enquiry to certificate.

Same five steps every time. Predictable, documented, and finished with a Certificate of Electrical Safety lodged with ESV.

  1. 01

    Enquiry

    Tell us the scope by phone or form. Same-day reply during business hours.

  2. 02

    Site visit

    We come on site to inspect, scope properly, and walk through options.

  3. 03

    Written quote

    Itemised, fixed-price quote in your inbox within one business day.

  4. 04

    Install

    Booked at your convenience. Tidy worksite, no hidden costs.

  5. 05

    Certified

    Certificate of Electrical Safety lodged with Energy Safe Victoria.

03Scope & standards

What's in a commercial fault finding & repairs job.

Commercial electrical faults rarely announce themselves cleanly. The symptom you see — RCD tripping at 2pm, fluorescents flickering on a Monday, freezer defrost cycling that throws the breaker — is downstream of a cause that needs systematic diagnosis. Millar Electrics applies the same diagnostic methods used in industrial maintenance: thermal imaging, insulation resistance, three-phase analysis, leakage logging, and elimination by isolation. The output is a written incident report with the cause identified, the rectification documented, and recommended preventative actions for the building's maintenance plan.

Common commercial faults we diagnose

Nuisance RCD trips on grouped RCDs from accumulated leakage; switchboard hot terminations identified on thermal imaging; three-phase imbalance causing neutral overheating; harmonics on lighting circuits causing nuisance tripping on Type AC RCDs; sub-main faults reading good on visual but failing under load; ground-loop currents in comms cabinets; degraded TPS cable in old industrial fit-outs; capacitor-bank failure in power-factor correction units. Each has a characteristic test signature once you know what to look for.

Diagnostic methods

Thermal imaging under load (FLIR-based) for switchboard and sub-board hot-spotting. Insulation resistance testing (megger) on isolated circuits to find degraded TPS or moisture-ingressed cabling. Earth fault loop impedance testing for fault-clearing time. Three-phase clamp-on analysis for balance and harmonics. RCD trip-time and trip-current testing under load. Leakage loggers connected over 24–72 hours for intermittent faults. We work the diagnostic ladder rather than guessing.

Reports and records

Every fault visit ends with a written incident report: time on site, work performed, parts used, test readings, photographs, and recommended preventative actions. Suitable for building managers, insurer audits, and owners corporation files. For prescribed work we lodge a Certificate of Electrical Safety with Energy Safe Victoria. Recurring fault-finding clients move onto maintenance contracts where we work the preventative side rather than reacting to incidents.

Standards we work to

Repair and rectification work is installed to AS/NZS 3000 (the Wiring Rules). Verification testing follows AS/NZS 3017 — insulation resistance, earth fault loop impedance, RCD trip-time and trip-current under load, polarity and continuity. Safe-work procedures while diagnosing energised commercial switchboards follow AS/NZS 4836, including isolation, lock-out, and live-work permits where unavoidable. Thermographic inspection follows the severity bands and reporting conventions described in our Thermographic Inspection service.

04Inclusions

What every job includes.

07 line items, every time. No surprise add-ons after acceptance.

  • 01Visual and thermal-imaging inspection of switchboards
  • 02Three-phase load and balance measurement under operating conditions
  • 03Insulation resistance and earth-fault loop impedance testing
  • 04RCD nuisance-trip cause analysis (DC fault currents, leakage currents, harmonics)
  • 05Sub-main and sub-board fault localisation
  • 06Repair or rectification, with documentation suitable for insurer / building manager
  • 07Written incident report with photographs and recommended preventative actions
05 / No-obligation quote

Free written quote in one business day.

We come to site, scope it, and email you a fixed price — no surprises after acceptance.

06Common questions

Before you book.

Answers to the questions we get most often. Anything not covered? Send through an enquiry — we'll reply same business day.

09Appendix

Related & spec.

BWhy Millar Electrics
Licensed
REC-22849
Insured
Public liability
Compliance
COES issued
Worksite
Tidy, no surprises
Coverage
Melbourne's east
Established
2016
10 / GET IN TOUCH

Ready to
book commercial fault finding & repairs?

Free quotes. We'll reply inside four business hours, or call straight back if you'd rather talk.